Leak alarm type LWG 2000 (WHG)
Leak detection system as:
- liquid sensor system in leakage or monitoring spaces of class III in accordance with EN 13160-1 with EN 13160-4
- safety device leak detection system according to German DWA-A 791
Use as:
- construction product as part of systems for the storage, filling and handling of water-endangering materials
- liquid sensor for the use in systems for the storage of fuels with a flashpoint above +55 °C which are intended for the supply of heating systems in buildings
- for the monitoring of a tank, a pipeline or a containment facility
- as an automatic fault signalling device according to German worksheet DWA-A 779
Operating media:
waste oil, diesel, FAME, liquid fertiliser, urea solution (AdBlue), fuel oil, fuel oil bio, industrial oil, oil/water mixture, vegetable oil, water and aqueous solutions of inorganic, non-oxidising salts with a pH between 6 and 8
- Potential-free relay contact to connect e.g. a burner pump, warning light or acoustic signal generator
- general building approval no. Z-65.40-357; thus adequate under water law requirements
- CE marking according to EMC, LVD and RoHS
- CE marking according to EU CPR: declaration of performance according to EN 13160-1 with EN 13160-4
- Belgium: VINCOTTE
- Switzerland: SVTI [Swiss Association for Technical Inspections] certificate
- supply voltage: 230 V AC 50 to 60 Hz
- power consumption: 2.5 VA
- sensor: metal-encapsulated PTC
- temperature range: -20 °C to +60 °C
- protection type: IP30
- The connection cable can be extended up to a maximum of 100 metres!