Excess flow valve low pressure

for connection to the outlet of the low pressure regulator, for protection of hose assemblies


  • prevents gas escape in case the hose assembly is damaged or becomes loose and closes the gas flow when the nominal flow rate is exceeded by 10%
  • automatic excess flow valve SBS/AU:
    opens automatically, which keeps gas leaks to a minimum and means delayed opening in the case of long hose assemblies
  • manual excess flow valve SBS/MA:
    no delay or leakage volume, but manual opening required

  • EC type examination certificate GAR

  • maximum permissible pressure: PS 16 bar

  • In accordance with the requirements of DGUV Regulation 110-010 (German statutory accident insurance, previously DGUV Regulation 79) hose assemblies longer than 400 mm must be secured with an excess flow valve SBS.
  • In accordance with DVGW worksheet G 612, hose assemblies longer than 1500 mm must be secured with an excess flow valve SBS.
  • Excess flow valves SBS with a working pressure of 29 mbar are not suitable for use in Germany!
Filter

Connection A
Connection B
Outlet pressure
Flow rate
Packaging
Part no.
G 1/4 lh nut
G 1/4 lh M
50 mbar
1.5 kg/h
6285000
G 1/4 lh nut
G 1/4 lh M
29 mbar
1.5 kg/h
6285002

Connection A
Connection B
Outlet pressure
Flow rate
Packaging
Part no.
G 1/4 lh nut
G 1/4 lh M
50 mbar
1.5 kg/h
6285302
G 1/4 lh nut
G 1/4 lh M
29 mbar
1.5 kg/h
6285303